LumaQuote Electrical calculators 3 phase power

3 Phase Power Calculator

Calculate three-phase power from line voltage, current and power factor: real power in kW, apparent power in kVA and reactive power in kVAR. Or work back from kW to the line current.

3 phase power formula

For a balanced three-phase load, power is 1.732 times the line-to-line voltage times the line current, times the power factor for real power.

kW = 1.732 × volts × amps × power factor ÷ 1,000

kVA = 1.732 × volts × amps ÷ 1,000

kVAR = kVA × √(1 − power factor²)

amps = kW × 1,000 ÷ (1.732 × volts × power factor)

Examples

  1. 100 A at 480 V, power factor 0.9: 1.732 × 480 × 100 × 0.9 = 74.8 kW. At power factor 1.0 it is 83.1 kW.
  2. 50 kW at 208 V, power factor 0.9: 50,000 ÷ (1.732 × 208 × 0.9) = 154.2 A per line.

Why 1.732?

The three phases peak a third of a cycle apart, so the voltage between two phases is the square root of 3 times the voltage from a phase to neutral. That is why 120 V to neutral gives 208 V between phases (120 × 1.732), 277 V gives 480 V, and 347 V gives 600 V.

Line and phase values in wye and delta

  • Wye (star): line current equals phase current, and line voltage is 1.732 × phase voltage. 208Y/120, 480Y/277 and 600Y/347 V are wye systems.
  • Delta: line voltage equals phase voltage, and line current is 1.732 × the current in each winding. 240 V and 480 V delta services are common in older industrial buildings.

Either way, the power formula is the same when you use line voltage and line current.

Three-phase kVA by current

Apparent power at common line-to-line voltages. Multiply by the power factor for kW.

Line current208 V240 V480 V600 V
10 A3.60 kVA4.16 kVA8.31 kVA10.39 kVA
20 A7.21 kVA8.31 kVA16.63 kVA20.78 kVA
30 A10.81 kVA12.47 kVA24.94 kVA31.18 kVA
50 A18.01 kVA20.78 kVA41.57 kVA51.96 kVA
100 A36.03 kVA41.57 kVA83.14 kVA103.9 kVA
200 A72.05 kVA83.14 kVA166.3 kVA207.8 kVA
400 A144.1 kVA166.3 kVA332.6 kVA415.7 kVA

Unbalanced loads

The formula assumes the three phases carry the same current. Lighting and receptacle panels are rarely perfectly balanced. For an unbalanced panel, work out each phase on its own (line-to-neutral volts × that phase's amps × power factor) and add them up.

Quoting lighting work?

LumaQuote is lighting audit and retrofit proposal software for electrical contractors. Count fixtures and take photos on site with the field app, even with no signal, then turn the audit into a priced proposal on your computer.

See the field app Start free

Free plan, no credit card. iPhone, iPad and Android.

3 phase power FAQ

How do you calculate 3 phase power?

Multiply 1.732 × line-to-line voltage × line current × power factor, then divide by 1,000 for kW. Leave out the power factor to get kVA.

What is 1.732 in three-phase calculations?

The square root of 3. It is the ratio between line-to-line and line-to-neutral voltage in a three-phase system, for example 208 ÷ 120.

How many kW is 100 amps three-phase at 480 V?

83.1 kW at power factor 1.0, or 74.8 kW at power factor 0.9.

How many amps is 50 kW three-phase at 208 V?

138.8 A at power factor 1.0, or 154.2 A at power factor 0.9.

Is the voltage in the formula line-to-line or line-to-neutral?

Line-to-line. A 480 V motor nameplate means 480 V between phases. If you only know the line-to-neutral voltage, multiply it by 1.732.

What is kVAR?

Reactive power, the part of the apparent power that flows back and forth without doing work. It comes mostly from motors and transformers, and capacitors are used to cancel it and raise the power factor.