LumaQuote Electrical calculators kVA calculator
kVA Calculator
Work out kVA from volts and amps, or the full-load current of a transformer from its kVA rating. Single-phase and three-phase, with the next standard transformer size.
How to calculate kVA
kVA is volts times amps, divided by 1,000. Three-phase adds the square root of 3 (1.732), with the line-to-line voltage.
Single-phase: kVA = volts × amps ÷ 1,000
Three-phase: kVA = 1.732 × volts × amps ÷ 1,000
Turn it around to get the current a transformer can deliver at full load:
Single-phase: amps = kVA × 1,000 ÷ volts
Three-phase: amps = kVA × 1,000 ÷ (1.732 × volts)
Examples
- 75 kVA three-phase at 208 V: 75,000 ÷ (1.732 × 208) = 208.2 A on the secondary.
- The same 75 kVA at 480 V: 75,000 ÷ (1.732 × 480) = 90.21 A on the primary.
- 50 kVA single-phase at 240 V: 50,000 ÷ 240 = 208.3 A.
Transformer full-load amps chart
Three-phase transformers
| Transformer | 208 V | 240 V | 480 V | 600 V |
|---|---|---|---|---|
| 15 kVA | 41.64 A | 36.08 A | 18.04 A | 14.43 A |
| 30 kVA | 83.27 A | 72.17 A | 36.08 A | 28.87 A |
| 45 kVA | 124.9 A | 108.3 A | 54.13 A | 43.30 A |
| 75 kVA | 208.2 A | 180.4 A | 90.21 A | 72.17 A |
| 112.5 kVA | 312.3 A | 270.6 A | 135.3 A | 108.3 A |
| 150 kVA | 416.4 A | 360.8 A | 180.4 A | 144.3 A |
| 225 kVA | 624.5 A | 541.3 A | 270.6 A | 216.5 A |
| 300 kVA | 832.7 A | 721.7 A | 360.8 A | 288.7 A |
| 500 kVA | 1,387.9 A | 1,202.8 A | 601.4 A | 481.1 A |
| 750 kVA | 2,081.8 A | 1,804.2 A | 902.1 A | 721.7 A |
| 1,000 kVA | 2,775.7 A | 2,405.6 A | 1,202.8 A | 962.3 A |
Single-phase transformers
| Transformer | 120 V | 240 V |
|---|---|---|
| 10 kVA | 83.33 A | 41.67 A |
| 15 kVA | 125.0 A | 62.50 A |
| 25 kVA | 208.3 A | 104.2 A |
| 37.5 kVA | 312.5 A | 156.3 A |
| 50 kVA | 416.7 A | 208.3 A |
| 75 kVA | 625.0 A | 312.5 A |
| 100 kVA | 833.3 A | 416.7 A |
| 167 kVA | 1,391.7 A | 695.8 A |
Full-load current at the rated voltage. Overcurrent protection for transformers follows its own rules (NEC Article 450, CEC Section 26), so use those tables to size the breakers.
kVA vs kW
kVA is apparent power, what the transformer and wiring have to carry. kW is the real power the loads use. The link between them is the power factor: kW = kVA × power factor. A 75 kVA transformer feeding loads at power factor 0.9 delivers about 67.5 kW. That is why transformers, generators and UPS units are rated in kVA: they have to carry the current whatever the power factor is.
How to size a transformer
- Add up the load in kVA. Use the panel schedule or a load calculation, not just the connected nameplates.
- Allow for continuous load and growth. Many designers add 25% so the transformer runs cooler and leaves room for added circuits. The calculator can add it for you.
- Pick the next standard size up. Three-phase dry types usually come in 15, 30, 45, 75, 112.5, 150, 225, 300 and 500 kVA.
- Check both sides. Size the primary and secondary protection and conductors from the full-load amps on each side.
Quoting lighting work?
LumaQuote is lighting audit and retrofit proposal software for electrical contractors. Count fixtures and take photos on site with the field app, even with no signal, then turn the audit into a priced proposal on your computer.
Free plan, no credit card. iPhone, iPad and Android.
KVA calculator FAQ
What is kVA?
Kilovolt-amps: volts times amps, divided by 1,000. It is the apparent power a transformer, generator or UPS has to carry, whatever the power factor of the load.
How many amps is a 75 kVA transformer?
208.2 A at 208 V three-phase and 90.21 A at 480 V three-phase.
How many amps is a 50 kVA single-phase transformer at 240 V?
208.3 A.
How do I convert kVA to kW?
Multiply by the power factor. At power factor 0.9, 100 kVA is 90 kW. At 1.0 they are equal.
What size transformer do I need?
Add up the load in kVA, add about 25% for continuous load and growth, then pick the next standard size. Confirm the overcurrent protection with NEC Article 450 (CEC Section 26 in Canada).
Is three-phase kVA calculated with line-to-line voltage?
Yes. Use the line-to-line voltage, such as 208 or 480 V, with 1.732 in the formula. If you only have line-to-neutral voltage, multiply it by 1.732 first.
Related calculators
- 3 Phase Power CalculatorkW, kVA and kVAR from line voltage and current.
- Amps to Watts CalculatorPower from current, with power factor.
- Watts to Amps CalculatorCurrent from power, for single-phase, three-phase and DC.
- Breaker Size CalculatorThe right breaker for a load, with the 125% rule.
- Lighting layout calculatorFixture count and foot-candles for a room.
- High bay lighting calculatorWarehouse fixture counts, spacing and savings.
- All electrical calculatorsEvery calculator on one page.